Property | Value |
---|---|
Item - Relay | Phase Monitor Relay |
Item | Phase Monitor Relay |
Input or Control Voltage | 480 to 600V AC |
AC Contact Rating - Relay | 10A @ 277V |
DC Contact Rating - Relay | 7A @ 30V |
Base Type - Plug In Relay | Octal |
Number of Pins - Relay | 8 |
Mounting - Relay | Plug In |
Contact Form - Relay | SPDT |
Pick Up Range | 460 to 600VAC |
Over Voltage | Fixed 110% of Line Voltage Setting |
Under Voltage | 432 to 540V AC |
Drop-Out Range | 80% to 95% |
Phase Loss Sensitivity | Yes |
Phase Loss Time Delay | 0.1 sec |
Phase Reversal | Yes |
Phase Reversal Time Delay | 0.1 sec |
Phase Unbalance | 2 to 10% |
Phase Unbalance Time Delay | 0.3 to 30.0 sec |
Restart | Auto, Manual |
Restart Time Delay | 1 to 300 sec |
Input or Control Voltage Range | 480 to 600VAC |
Contact Amp Rating (Resistive) | 10 |
Input Voltage | 460 to 600V AC |
Body Height - Relay | 2.9 in |
Contact Form | SPDT |
Phase | 3 |
Overall Height - Relay | 3.0 in |
Socket | 5X852 |
Number of Contacts | 1 |
Trip Delay | Power Up and Restart After Fault Clear: 1.00 to 300.0 sec., Phase Loss and Reversal: 100 msec., Phase Unbalance: 0.30 to 30.0 sec., Undervoltage: 0.30 to 30.0 sec., Overvoltage: 0.30 to 30.0 sec. |
Body Width - Relay | 1.7 in |
Pins | 8 |
Base Type | Octal |
Body Depth - Relay | 2.4 in |
Standards | CE Certified, cULus Listed, cURus |
For Use With | Sensors |
Body Height | 2.4 in |
Body Width | 1.7 in |
Minimum Operating Temperature | -18.4 Degrees F |
Socket Code | A |
Overvoltage | Fixed 110% of Line Voltage Setting |
Contact Rating (DC) | 7 A @ 30V |
Mounting Style | Plug-In |
Overall Depth | 2.4 in |
Number of Pins | 8 |
Monitored Parameters | Overvoltage, Phase Loss, Phase Reversal, Phase Unbalance, Undervoltage |
Maximum Switching Capacity | 40 VA |
Frequency | 50/60 Hz |
Mechanical Operating Durability | 10,000,000 |
Maximum Switching Voltage | 660V |
Contact Rating (AC) | 10 A @ 277V |
Electrical Operating Durability | 100,000 |
Base Shape | Octal |
Maximum Operating Temperature | 149 Degrees F |
Body Depth | 2.9 in |
Undervoltage | 460 to 600V AC |
Current Rating | 10 A |
Power Consumption | 40 VA |
Minimum/Maximum Voltage | 156-550V (PMPU); 77-152V (PMP120): 345-660V (PMP575), 50-60Hz.±5% |
Output Contacts | 10A @ 277V AC / 7A @ 30V DC; |
Configuration / Contact Rating | SPDT. 10A @ 277V AC / 7A @ 30V DC |
Enclosure Style | Plug-in case utilizing industry-standard 8 pin octal sockets, Plug-in |
Load (Burden) | Less than 40 VA |
Monitored Voltage | 460-600V AC |
Life | Mechanical: 10,000,000 operations, Full Load: 100,000 operations |
Temperature | -28°to 65°C (-18°to 149°F) |
Reset | As standard, the PMP Series relays are in the Automatic Reset mode. However, they can be set in the Manual Reset mode by connecting an external N.C. switch across terminals 6 and 7. Upon application of line voltage, the PMP Series will go into Manual Reset mode if it recognizes a closure across terminals 6 and 7. After a fault clears, the relay will not reset until the N.C. switch is opened. |
Output | 10A SPDT |
Protection | Phase Loss, Phase Reversal, Voltage Unbalance, Undervoltage u0026 Overvoltage |
Country of Origin (subject to change) | United States |
Package Quantity | 1 |
3 Phase Monitor Relay, SPDT, 600VAC, 8 Pin, Macromatic, Mfr#: PMP575
$86,40
Free shipping will be applied on orders over $50
Phase Monitor Relay, Base Shape Octal, Contact Form SPDT, Contact Rating (AC) 10 A @ 277V, Contact Rating (DC) 7 A @ 30V, Current Rating 10 A, Input Voltage 460 to 600V AC, Monitored Parameters Overvoltage, Phase Loss, Phase Reversal, Phase Unbalance, Undervoltage, Number of Pins 8, Restart Auto, Manual, Restart Time Delay 1 to 300 sec, Mounting Style Plug-In, Body Depth 2.9 in, Body Height 2.4 in, Body Width 1.7 in, Electrical Operating Durability 100,000, For Use With Sensors
9999 in stock
Must order in multiples of 1
Subtotal:
$86.4
You must be logged in to post a review.
Reviews
There are no reviews yet.