Property | Value |
---|---|
Item | IEC Magnetic Contactor |
Full Load Amps-Inductive | 150 A |
Full Load Amps-Resistive | 200 A |
Action | Non-Reversing |
Number of Poles | 3 |
Coil Volts | 24 V DC |
Reversing | No |
Height | 4.33 in |
Width | 4.33 in |
HP @ 3 Phase - 240V | 50 hp |
Depth | 5.12 in |
HP @ 3 Phase - 575V | 125 hp |
HP @ 3 Phase - 208V | 40 hp |
HP @ 3 Phase - 480V | 100 hp |
Enclosure NEMA Rating | No Enclosure |
Aux. Contact Configuration | 1NO/1NC |
Hz | 50/60 |
Standards | BV, CCC, CSA, CSA C22.2 No 14, DNV, EN 60947-4-1, EN 60947-5-1, GL, GOST, IEC 60947-4-1, IEC 60947-5-1, LROS, RINA, UKCA, UL 508, UL Listed |
Frame / Series / Class / Code | TeSys |
Auxiliary Contact Form | 1NO/1NC |
Series | TeSys Deca |
NEMA Size | Not Applicable |
IP Rating | IP20 |
Thermal Amperage | 200 A (at 60°C Power Circuit) |
Rated Breaking Capacity | 1400 A @ 440V |
Fuse Amps | 10 A (Signalling Circuit), 315 A (Type 1 Power Circuit), 250 A (Type 2 Power Circuit) |
Signalling Circuit Frequency | 25 to 400 Hz |
Rated Voltage | 1000V AC, 300V DC |
Mounts On | Plate, Rail |
Overvoltage Category | CAT III |
Non-Overlap Time | 1.5 ms |
Net Weight | 2.5 kg |
Environmental Attributes | Mercury Free, PVC Free, Pollution Degree 3 |
Shock Resistance | 15 G for 11 ms (Contactor Closed), 6 G for 11 ms (Contactor Open) |
Tightening Torque | 1.2 Nm (Control Circuit), 12 Nm (Power Circuit) |
Rated Short-Time Withstand Current | 250 A (at 40°C for 10 min Power Circuit), 580 A (at 40°C for 1 min Power Circuit), 1200 A (at 40°C for 10 s Power Circuit), 1400 A (at 40°C for 1 s Power Circuit), 100 A (For 1 s Signalling Circuit), 120 A (For 500 ms Signalling Circuit), 140 A (For 100 ms Signalling Circuit) |
Working Height | Up to 9842.52 ft |
Operating Time | 20 to 35 ms (Closing), 40 to 75 ms (Opening) |
Electrical Durability | 0.85 Mcycles (150 A, AC-3, Less than 440 V); 1 Mcycles (200 A, AC-1, Less than 440 V); 0.85 Mcycles (150 A, AC-3e, Less than 440 V) |
Max. Temperature | 850°C |
Mechanical Durability | 8 Mcycles |
Switching Current | 5 mA (Signalling Circuit) |
Fire Rating | UL 94 V1 |
Insulation Resistance Range | Greater Than 10 MOhms (Signalling Circuit) |
Features | With Integral Suppression Device |
Vibration Resistance | 4 G (Contactor Closed), 2 G (Contactor Open) |
Rated Insulation Volts | 600/1000V (Power Circuit), 600/690V (Signalling Circuit) |
Max. Operating Watts | 40 kW (at 220 to 230V AC 50/60 Hz AC-3), 75 kW (at 380 to 400V AC 50/60 Hz AC-3), 80 kW 415 to (at 440V AC 50/60 Hz AC-3), 90 kW (at 500V AC 50/60 Hz AC-3), 100 kW (at 660 to 690V AC 50/60 Hz AC-3), 75 kW (at 1000V AC 50/60 Hz AC-3), 22 kW (at 400V AC 50/60 Hz AC-4), 40 kW (at 220 to 230V AC 50/60 Hz AC-3e), 75 kW (at 380 to 400V AC 50/60 Hz AC-3e), 80 kW (at 415 to 440V AC 50/60 Hz AC-3e), 90 kW (at 500V AC 50/60 Hz AC-3e), 100 kW (at 660 to 690V AC 50/60 Hz AC-3e), 75 kW (at 1000V AC 50/60 Hz AC-3e) |
Switching Voltage | 17 V (Signalling Circuit) |
Operating Speed | 1200 cycles per hr |
Electrical Connection | Screw Clamp Terminals |
Includes Protective Cover | Yes |
Impulse Withstand Voltage | 8 kV |
Application | Motor Control, Resistive Load |
Rated Making Capacity | 140 A (AC Signalling Circuit), 250 A (DC Signalling Circuit), 1660 A @ 440V (Power Circuit) |
Control Circuit Voltage Limits | Operational DC: 0.75 to 1.2 Uc (at -40 to 55°C), 1 to 1.2 Uc (at 55 to 70°C); Drop-Out DC: 0.15 to 0.4 Uc (at -40 to 70°C) |
Impedance | 0.6 mOhm |
Coil Voltage | 24V DC |
Horsepower @ Single Phase - 240V AC | 3 hp |
Minimum Operating Temperature | -40 Degrees F |
Embedded Surge Suppressor | Yes |
Phase | Three |
Full Load Current - Resistive | 200 A |
Overall Depth | 5.35 in |
Overall Width | 0.47 in |
Horsepower @ Three Phase - 600V AC | 125 hp |
Mounting Style | DIN Rail, Plate |
Horsepower @ Three Phase - 240V AC | 50 hp |
Electrical Operating Durability | 1,000,000, 850,000 |
NEMA Enclosure Rating | No Enclosure |
Contactor Style | IEC |
Number of Auxillary Contacts | 2 |
Overall Height | 6.22 in |
Horsepower @ Three Phase - 480V AC | 100 hp |
Terminal Connection Type | Screw Clamp Terminals |
Resistance Properties | Fire Resistant, Insulation Resistant |
Full Load Current - Inductive | 150 A |
Reversing Capability | Non-Reversing |
Maximum Operating Temperature | 140 Degrees F |
Includes Auxiliary Contacts | Yes |
NEMA Enclosure Material | Not Applicable |
Horsepower @ Three Phase - 208V AC | 40 hp |
Maximum Voltage Rating | 1000V AC |
Frequency | 50/60 Hz |
Number of Normally Open Main Contacts | 3 |
Mechanical Operating Durability | 8,000,000 |
Power Dissipation Per Pole | 24 W AC-1; 13.5 W AC-3; 13.5 W AC-3e |
Average Impedance | 0.6 mOhm - Ith 200 A 50 Hz for power circuit |
Pole Contact Composition | 3 NO |
Rated Operational Voltage | Power circuit Less than or Equal to 1000 V AC 25 to 400 Hz; Power circuit Less than or Equal to 300 V DC |
IRMS Rated Making Capacity | 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1; 1660 A at 440 V for power circuit conforming to IEC 60947 |
Minimum Switching Current | 5 mA for signalling circuit |
Minimum Switching Voltage | 17 V for signalling circuit |
Safety Reliability Level | B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1 |
IP Degree Of Protection | IP20 front face IEC 60529 |
Product Certifications | UL; BV; GL; GOST; CSA; CCC; LROS (Lloyds register of shipping); RINA; DNV; UKCA; CE |
Maximum Operating Rate | 1200 cyc/h 140°F (60°C) |
Compatibility Code | LC1D |
Mechanical Robustness | Vibrations contactor open 2 Gn, 5 to 300 Hz); Vibrations contactor closed 4 Gn, 5 to 300 Hz); Shocks contactor closed 15 Gn for 11 ms); Shocks contactor open 6 Gn for 11 ms) |
Rated Insulation Voltage | Power circuit 600 V CSA; Power circuit 600 V UL; Power circuit 1000 V IEC 60947-4-1; Signalling circuit 690 V IEC 60947-1; Signalling circuit 600 V CSA; Signalling circuit 600 V UL |
Permissible Ambient Air Temperature Around The Device | -40 to 140°F (-40 to 60°C); 140 to 158°F (60 to 70°C) with derating |
Pollution Degree | 3 |
Contactor Application | Resistive load; Motor control |
Product Or Component Type | Contactor |
Auxiliary Contact Composition | 1 NO + 1 NC |
Auxiliary Contacts Type | Mechanically linked 1 NO + 1 NC IEC 60947-5-1; Mirror contact 1 NC IEC 60947-4-1 |
Utilisation Category | AC-3; AC-4; AC-1; AC-3e |
Contact Compatibility | M10 |
Poles Description | 3P |
Connections - Terminals | Control circuit: screw clamp terminals 2 0.00 to 0.00 in² (1 to 2.5 mm²) - cable stiffness: flexible with cable end; Control circuit: screw clamp terminals 1 0.00 to 0.00 in² (1 to 2.5 mm²) - cable stiffness: flexible with cable end; Control circuit: screw clamp terminals 1 0.00 to 0.00 in² (1 to 2.5 mm²) - cable stiffness: flexible without cable end; Control circuit: screw clamp terminals 2 0.00 to 0.00 in² (1 to 2.5 mm²) - cable stiffness: flexible without cable end; Control circuit: screw clamp terminals 1 0.00 to 0.00 in² (1 to 2.5 mm²) - cable stiffness: solid without cable end; Control circuit: screw clamp terminals 2 0.00 to 0.00 in² (1 to 2.5 mm²) - cable stiffness: solid without cable end; Power circuit: connector 1 0.02 to 0.19 in² (10 to 120 mm²) - cable stiffness: flexible without cable end; Power circuit: connector 2 0.02 to 0.08 in² (10 to 50 mm²) - cable stiffness: flexible without cable end; Power circuit: connector 1 0.02 to 0.19 in² (10 to 120 mm²) - cable stiffness: flexible with cable end; Power circuit: connector 2 0.02 to 0.08 in² (10 to 50 mm²) - cable stiffness: flexible with cable end; Power circuit: connector 1 0.02 to 0.19 in² (10 to 120 mm²) - cable stiffness: solid without cable end; Power circuit: connector 2 0.02 to 0.08 in² (10 to 50 mm²) - cable stiffness: solid without cable end |
Mounting Support | Rail; Plate |
Conventional Free Air Thermal Current | 200 A (at 140°F (60°C)) for power circuit |
Protective Treatment | THIEC 60068-2-30 |
Rated Short Time Withstand Current | 250 A 104°F (40°C) - 10 min for power circuit; 580 A 104°F (40°C) - 1 min for power circuit; 1200 A 104°F (40°C) - 10 s for power circuit; 1400 A 104°F (40°C) - 1 s for power circuit; 100 A - 1 s for signalling circuit; 120 A - 500 ms for signalling circuit; 140 A - 100 ms for signalling circuit |
Rated Impulse Withstand Voltage | 8 kV IEC 60947 |
Rated Operational Current | 200 A (at Less than 140°F (60°C)) at Less than or Equal to 440 V AC AC-1 for power circuit; 150 A (at Less than 140°F (60°C)) at Less than or Equal to 440 V AC AC-3 for power circuit; 150 A (at Less than 140°F (60°C)) at Less than or Equal to 440 V AC AC-3e for power circuit |
Insulation Resistance | Greater than 10 MOhm for signalling circuit |
Climatic Withstand | IACS E10 exposure to damp heat |
Operating Altitude | 0 to 9842.52 ft (0 to 3000 m) |
Associated Fuse Rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 315 A gG at Less than or Equal to 690 V coordination type 1 for power circuit; 250 A gG at Less than or Equal to 690 V coordination type 2 for power circuit |
Hold-In Power Consumption in W | 2.4 to 5.1 W 68°F (20°C) |
Control Circuit Type | DC standard |
Inrush Power in W | 270 to 365 W 68°F (20°C)) |
Flame Retardance | V1 conforming to UL 94 |
Maximum Horse Power Rating | 40 hp at 200/208 V AC 50/60 Hz for 3 phase motors; 50 hp at 230/240 V AC 50/60 Hz for 3 phase motors; 100 hp at 460/480 V AC 50/60 Hz for 3 phase motors; 125 hp at 575/600 V AC 50/60 Hz for 3 phase motors |
Fire Resistance | 1562°F (850°C) IEC 60695-2-1 |
Motor Power KW | 40 kW at 220 to 230 V AC 50/60 Hz (AC-3); 75 kW at 380 to 400 V AC 50/60 Hz (AC-3); 80 kW at 415 to 440 V AC 50/60 Hz (AC-3); 90 kW at 500 V AC 50/60 Hz (AC-3); 100 kW at 660 to 690 V AC 50/60 Hz (AC-3); 75 kW at 1000 V AC 50/60 Hz (AC-3); 22 kW at 400 V AC 50/60 Hz (AC-4); 40 kW at 220 to 230 V AC 50/60 Hz (AC-3e); 75 kW at 380 to 400 V AC 50/60 Hz (AC-3e); 80 kW at 415 to 440 V AC 50/60 Hz (AC-3e); 90 kW at 500 V AC 50/60 Hz (AC-3e); 100 kW at 660 to 690 V AC 50/60 Hz (AC-3e); 75 kW at 1000 V AC 50/60 Hz (AC-3e) |
Protective Cover | With |
Time Constant | 25 ms |
Country of Origin (subject to change) | Czechia |
Package Quantity | 1 |
IEC Magnetic Contactor, 3 Poles, 24 V DC, 150 A, Reversing: No, Square D, Mfr#: LC1D150BD
$728,99
Free shipping will be applied on orders over $50
IEC Magnetic Contactor, Auxiliary Contact Form 1NO/1NC, NEMA Enclosure Rating No Enclosure, NEMA Size Not Applicable, Coil Voltage 24V DC, Number of Poles 3, Full Load Current - Inductive 150 A, Full Load Current - Resistive 200 A, Reversing Capability Non-Reversing, Overall Height 6.22 in, Overall Width 0.47 in, Terminal Connection Type Screw Clamp Terminals, Mounting Style DIN Rail, Plate, Series TeSys Deca, Number of Auxillary Contacts 2, Contactor Style IEC
9999 in stock
Must order in multiples of 1
Subtotal:
$728.99
You must be logged in to post a review.
Reviews
There are no reviews yet.