Property | Value |
---|---|
Coil Volts | 600VAC |
Item | Control Relay 600Vac 10Amp Iec +Options |
Standards | EN/IEC 60947-4-1 || GB/T 14048.4 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1 |
[Ith] Conventional Free Air Thermal Current | 10 A 50°C |
Height | 58 mm |
Maximum Operating Rate | 10000 cyc/h |
Connections - Terminals | screw clamp terminals 1 1.5-4 mm²solid || screw clamp terminals 2 1.5-4 mm²solid || screw clamp terminals 1 0.75-4 mm²flexible with cable end || screw clamp terminals 2 0.75-4 mm²flexible without cable end || screw clamp terminals 1 0.34-1.5 mm²flexible with cable end || screw clamp terminals 2 0.34-1.5 mm²flexible without cable end |
Product Certifications | CB Scheme || CCC || UL || CSA || EAC || CE || UKCA |
Mechanical Robustness | vibrations contactor open2 Gn, 5...300 Hz IEC 60068-2-6 || vibrations contactor closed4 Gn, 5...300 Hz IEC 60068-2-6 || shocks contactor open10 Gn for 11 ms IEC 60068-2-27 || shocks contactor closed15 Gn for 11 ms IEC 60068-2-27 |
Mechanical Durability | 10 Mcycles |
Protective Treatment | TC IEC 60068 |
Ambient Air Temperature For Operation | -25-50°C |
Hold-In Power Consumption In Va | 4.5-4.5 VA 20°C) |
Depth | 57 mm |
Product Or Component Type | control relay |
Device Short Name | CA2K |
[Ui] Rated Insulation Voltage | 690 V IEC 60947 || 750 V VDE 0110 group C || 690 V BS 5424 || 600 V CSA C22.2 No 14 |
Non Overlap Distance | 0.5 mm |
Mounting Support | plate || rail |
Minimum Switching Current | 5 mA |
Associated Fuse Rating | 10 A gG IEC 60947 || 10 A gG VDE 0660 |
Flame Retardance | V1 conforming to UL 94 || requirement 2 conforming to NF F 16-101 || requirement 2 conforming to NF F 16-102 |
Irms Rated Making Capacity | 110 A IEC 60947 |
Immunity To Microbreaks | 2 ms |
Operating Time | 10...20 ms coil de-energisation and NO opening || 10...20 ms coil energisation and NO closing |
Range | TeSys |
[Ue] Rated Operational Voltage | u003c= 690 V u003c= 400 Hz |
Minimum Switching Voltage | 17 V |
Control Circuit Voltage Limits | drop-out 0.2...0.75 Uc 50°C) || operational 0.8...1.15 Uc 50°C) |
Product Name | TeSys CAK |
Tightening Torque | 1.3 N.m screw clamp terminals flat Ø 6 mm || 1.3 N.m screw clamp terminals Philips No 2 6 mm || 1.3 N.m screw clamp terminals pozidriv No 2 |
Pole Contact Composition | 4 NO |
Heat Dissipation | 1.3-1.3 W |
Width | 45 mm |
Ip Degree Of Protection | IP2X |
[Uc] Control Circuit Voltage | 220...230 V AC 50/60 Hz |
Ambient Air Temperature For Storage | -50-80°C |
Operating Altitude | 6561.68 ft (2000 m) without derating |
Inrush Power In Va | 30-30 VA 20°C) |
Utilisation Category | AC-15 || DC-13 |
Contactor Application | control circuit |
Insulation Resistance | u003e 10 MOhm |
Control Circuit Type | AC 50/60 Hz |
Country of Origin (subject to change) | Indonesia |
Package Quantity | 1 |
Control Relay 600Vac 10Amp Iec +Options, Schneider Electric, Mfr#: CA2KN40M7
$37,75
Free shipping will be applied on orders over $50
Control Relay 600Vac 10Amp Iec +Options
9999 in stock
Must order in multiples of 1
Subtotal:
$37.75
You must be logged in to post a review.
Reviews
There are no reviews yet.